Toronto Fire Services appealed a decision of the Fire Marshal rescinding an inspection order issued to the respondent property owner.
The order required the owner to replace windows surrounding third-floor balconies to protect occupants using the balconies as areas of refuge during a fire.
The Fire Marshal had rescinded the order because the balconies were previously approved as a compliance alternative.
The Fire Safety Commission found that while the previous approvals exempted the building from strict retrofit requirements, the inspector's broad powers to order fire safety measures justified requiring protection for the third-floor windows directly exposing the balconies.
However, the Commission found that windows on lower floors did not require protection given the building's fire alarm system and protected primary exits.
The Commission amended the Fire Marshal's decision to require protection only for the third-floor windows, while allowing the owner to submit alternative compliance options.